August 2010 |
[an error occurred while processing this directive] |
VFD Retrofit Opportunities Variable frequency drive
opportunities abound! |
|
Aahh, the V-F-D! Once a bone of contention, with its bulky footprint and less-than-reliable functionality, now a ubiquitous element in our everyday HVAC world. Since their inception, VFDs have come a long way, in terms of price, size, and reliability. So far have they come, you wonder why all motor-driven equipment isn’t required to have one. In fact, we might not be so far off from that, and with so many reasons to equip a motor with a VFD, it may soon become the norm rather than the exception, even with equipment traditionally not thought of as ever needing one. Consider this:
• Only about 1 in 10 “HVAC duty” electric motors are on VFDs
• Most pump and fan systems are oversized to account for maximum loads
• Capacity usually exceeds demand
• Power is proportional to the change in speed cubed (reduced speed = big savings).
[an error occurred while processing this directive] |
[an error occurred while processing this directive] |
Throw in the fact that, depending on where you live
and do business, there are incentive and rebate programs offering “money back”
for installing VFDs, and you have yourself all kinds of good reasons for
utilizing VFDs on existing motors. Following are a few of the more common
strategies that we find in our biz.
VFD to Replace Inlet Guide Vanes
This is the classic opportunity for installing a VFD. Inlet guide vanes (IGVs)
are commonly found on older, larger air handling equipment installed prior to
the development of reliable VFDs. IGVs are actuator-driven, either electrically
or pneumatically, to vary the volume of air that a fan can deliver. Without
getting into a discussion on the physical attributes of IGVs, suffice it to say
that the use of IGVs isn’t extremely energy-efficient.
A VFD retrofit in this application entails either complete removal of the IGVs,
or more typically, removing the actuator and pinning the guide vanes wide open.
The VFD is installed on the motor, and the control signal that drove the IGV
actuator is fed to the VFD as the “speed reference signal”. Pretty much all
there is to it. The VFD also needs a run command, in the form of a contact
closure, and in turn can give a status or alarm point, also in the form of a
contact closure. Your I/O device will need at least one extra output, for the
run command, and if it has any extra inputs, it can accommodate the status
and/or alarm points.
VFD on Exhaust Fan
Any constant speed exhaust fan can be put on a VFD, however not every
opportunity makes sense to do so. A larger fan serving multiple spaces by means
of a ductwork distribution system may be a good candidate. Or even a roof
mounted “general exhaust” fan serving, for example, an open warehouse or factory
space. In this opportunity, typically these fans are constant volume and run
continuously, with no regard for what’s happening in the space. Yet there may be
ample opportunity to “dial down” the amount of air being exhausted from the
space, either manually via operator intervention, or automatically to maintain
some temperature and/or pressure setpoint. See it now? Good, now go ahead and
make it happen!
VFD on Constant Volume Air Handling Unit
Just because an air handling system is designed to serve a single zone, doesn’t
necessarily mean that the fan needs to operate at “constant volume”. There are
opportunities for running this type of air handler at less than full capacity,
for sure. Like the exhaust fan opportunities discussed above, there may be times
when the fan simply does not need to run at full speed. These opportunities need
to be identified, so that the justification can be made to install a VFD, and
the control sequences can be generated and implemented in order to take
advantage of these opportunities.
VFD on Constant Volume Packaged RTU
Same concept as above, however maybe not as “cleanly” done. With a packaged
rooftop unit, one that sits outdoors and is virtually self-contained, the
concept of equipping the supply fan with a VFD requires careful consideration.
Yet it can be done. Things to consider: can the VFD fit inside an electrical
compartment of the unit? If so, the VFD may need to be rated for ambient
temperatures. If not, the VFD can be mounted to the side of the unit, however it
then also needs to be rated for the elements. As a last resort, the VFD can be
located indoors, remotely from the rooftop unit, but of course this has its
drawbacks as well. Operationally, unlike with the air handling unit discussed
previously, which is more typically equipped with hot and chilled water coils, a
packaged rooftop unit will come standard with gas-fired heating and DX cooling,
requiring that a minimum volume of air be delivered through the unit for all
heating/cooling cycles. That minimum may be high compared to the turndown that
the VFD can offer, but it still beats running the fan at full bore for all
periods of operation.
VFDs on Cooling Tower Fans
This is a very popular opportunity, especially with older chilled water systems,
whose cooling tower fans were originally installed without VFDs, and were
controlled as “on-off” in order to maintain condenser water temperature setpoint.
Install the VFD indoors as possible, and intercept the power wiring out to the
fan motor. Control the VFD in typical PID fashion to maintain a leaving
condenser water temperature setpoint. If there is more than one fan, then
sequence the control of the fan motor VFDs, so that the first one ramps up to
full speed before the second one begins its ascent. It is such a simple concept,
and one so easily implemented, that we’ll be seeing this scheme of control
applied not only with cooling towers, but with air cooled condensers and
condensing units as well, wherein typically numerous fans complete the package.
[an error occurred while processing this directive]
VFDs on HW/CHW pumps
In many older “single loop” hydronic systems, three-way valves were used at the
“appliance level” (unitary heaters, fan-coils, VAVs, etc), ensuring that the
main system pump(s) would constantly deliver full flow and not ever be subject
to a “deadheading” situation. Times have changed. If you see a new construction
project designed in this manner, call the engineer and demand a redesign!
Seriously though, the opportunities for these existing systems are out there.
The easiest thing to do is to physically (and permanently) close off the bypass
port at each and every three-way valve, save for the last one or two on any
branch line, so as to provide for a minimum amount of flow at all times
throughout the entire piping system. Exercise special caution with chilled water
systems, in regard to variable pumping through the chiller. There is a minimum
flow rate that the chiller evaporator is rated at, and it must be maintained.
Often with new construction projects, VFDs will be specified for the chilled
water pumps, along with a bypass valve that modulates open to maintain the
minimum required flow.
VFDs on CW Pumps
So here I am reviewing a large plan/spec project, and I notice that there are
VFDs specified for the condenser water pumps. I do believe that that’s the first
time I’ve seen this, yet I’m pretty darn certain that it won’t be the last. Kind
of the “last bastion” of constant speed / constant volume operation in HVAC, the
water flow through a water cooled chiller’s condenser bundle has historically
been specified to be such, and with good reason, seeing that your chiller
manufacturers are insisting that you maintain constant condenser water flow
through their machines. And I have to admit that I agree with the requirement,
but here I am reading a specification and there it is in black and white: VFDs
for the CW pumps! I will say that there is no specified type of control with
regard to varying the speed of the pumps, so maybe the VFDs are here simply for
the “soft start” functionality of the pump motors. And maybe, just maybe,
there’s a little “wiggle room” here, in which the pump speed, and therefore the
condenser water flow, can be turned down just a touch. Hey, any little bit
helps, and seeing that pumps (and fans for that matter) are typically oversized
to begin with, there may be some true justification for equipping these pumps
with VFDs. Just exercise caution, or you’ll find yourself tripping the unit out
on its internal safeties (or worse!).
Other VFD Opportunities
Now that you’re in tune with the concept, let you’re imagination take over!
Installing VFDs is certainly by no means restricted to HVAC equipment. Other
non-HVAC equipment (domestic water pumps come to mind) can be operated from a
variable frequency drive. You need to weigh the options and see if it makes
sense, of
course. Smaller motors are typically not real good candidates, as are motors
that are “maxxed” out, meaning that there is no real opportunity to turn down
the operation and therefore no real payback for installing a VFD. But still,
there are many opportunities out there, so let your mind wander, and go out
there and find them!
Tip of the Month: Spreadsheets and programs are available that help calculate savings when applying a VFD to an existing motor. These programs take into account the following: motor horsepower (HP), average daily/yearly use (hrs), and cost of electricity ($/kWh). Given this info, an“order of magnitude” can be figured, in terms of energy used with/without a VFD, and cost savings per year by using a VFD. For example, a VFD installed on a 10 HP motor that’s in use 4,200 hours per year, given Illinois electricity rates of approximately 9 cents per kilowatt hour, can yield a yearly savings of upwards of $1,500.00. That’s no small change! |
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The Automator] [About] [Subscribe ] [Contact Us]