August 2013 |
[an error occurred while processing this directive] |
And Another Collection of Short Stories
An ongoing series of tales told and lessons learned |
Steven
R. Calabrese |
Articles |
Interviews |
Releases |
New Products |
Reviews |
[an error occurred while processing this directive] |
Editorial |
Events |
Sponsors |
Site Search |
Newsletters |
[an error occurred while processing this directive] |
Archives |
Past Issues |
Home |
Editors |
eDucation |
[an error occurred while processing this directive] |
Training |
Links |
Software |
Subscribe |
[an error occurred while processing this directive] |
Continuing from June’s installment of this column, I present the next
in an ongoing series of shorts, fueled by email suggestions and
real-life experience.
Using CO2 to Detect Human Life
Simply put, we humans off-gas the stuff! In (not-so) scientific terms,
the concentration of carbon dioxide (CO2) in the great outdoors is
relatively constant at around 400 parts per million (ppm). When an
occupied indoor space is ventilated with the generally mandated 15
cubic feet per minute (CFM) of fresh air per occupant, the indoor CO2
level stabilizes at approximately 700 ppm above the outdoor air level,
or around 1,100 ppm. So there is a direct correlation between the level
of CO2 in an occupied space, and the occupancy level. Now, we don’t use
the CO2 level measured to do a “hard count” of the number of people in
the space. However, if we were to theorize that these values are
“firm”, and given that we’re modulating the outside air damper to
maintain a 1,100 ppm CO2 level “setpoint”, then theoretically we can
measure the amount of outside air being brought in via the outside air
damper, and correlate that to the number of people in the space served.
For example, if we were to use an airflow measuring station at the
outside air intake, and this device measured a flow rate of, say, 90
CFM, then we conclude that there are six people in the space served (15
CFM x 6 = 90). If three occupants were to vacate, the CO2 level in the
space would tend to drop, and thus the outside air damper would be
modulated to bring in less fresh air, until it stabilized at 45 CFM.
The above discussion is simply “food for thought”, but it does
demonstrate the theory behind using CO2 level to detect occupancy and
thus to properly and adequately ventilate indoor spaces. When utilized
in this manner, the process is termed Demand Controlled Ventilation,
and although it does have its limitations, it’s a step up from just
opening up the outside air damper to satisfy the maximum occupancy
level, with no regard as to the actual “real-time” occupancy level.
Determining the Number of Stages for Electric Duct Heaters
Determining the number of stages of electric heat requires looking at
the total delta T of the particular heating coil, as well as
considering the degree of control required. For precise temperature
control, the delta T per stage should be no more than five degrees. For
mediocre control, the delta T per stage can be in the range of 6-12
degrees, and for coarse control, 13 degrees and up. A good rule of
thumb is, 10 degrees per stage, for mediocre control.
It’s a common misconception that the larger the electric duct
heater, the more stages of control are needed. Yet from the above
discussion, we see that the number of stages is more or less a function
of the total delta T and the desired delta T per stage. A 20 KW
electric duct heater handling 3,150 CFM of air yields the same delta T
as a 3 KW heater handling 475 CFM of air: 20 degrees. Thus, given the
same application, both of these heaters can be supplied with simple
two-stage control.
The whole origin of the “mediocre control” rule of thumb stems from the
notion that the larger the delta T per stage, the more noticeable the
difference in supply air temperatures is when staging takes place. With
a 10 degree delta T per stage, the occupant may be more likely to feel
the difference when a stage of control is added or dropped out. The
larger the difference is, the more likely he/she is to feel the
difference. This is normally an undesirable and often an unacceptable
condition for HVAC comfort control. For more critical applications, the
delta T per stage should be lessened, by increasing the number of
stages.
What’s Your Comfort Range?
Everyone has one…a range of temperature that they feel comfortable
with. Some individuals’ ranges are larger than others. As well, ranges
differ from one individual to another. I can tell you that I can be
comfortable through a relatively large range of indoor temperatures,
meaning that it takes a real departure from the standard “room
temperature” of 72 degrees for me to complain. I fare better on the
cold side than on the warm side, for if it gets too warm, my head
starts to sweat, hot blooded as I am! Must get that from my mother’s
side…she likes it cold. Thinking that her comfort range is more like
60-65 degrees!
Of course on the other end of that spectrum are those folks who like it
on the warm side, like 74 degrees on up. You can begin to understand
the reason why service departments have their hands full with so many
hot and cold calls. It’s not so much that the equipment is
malfunctioning. Oftentimes it’s more so that the occupants of a more or
less common space have different comfort ranges. It’s just human
nature. Some like it hot, and some like it cold…so what’s your comfort
range?
Seasonal Setpoints
So we just got done discussing individual comfort range, and how that
relates to the accepted “room temperature setpoint”. However
thermostats don’t typically operate to maintain a precise setpoint.
This is especially true for staged thermostats, those of which operate
rooftop units and residential heating and air conditioning systems.
What you typically get, when you set your home thermostat, are two
setpoints separated by a deadband. For instance, in the summer you
might set the cooling setpoint to 72 degrees, which may automatically
establish the heating setpoint as 70 degrees (2-degree deadband). When
the space temperature is within deadband, all is well and neither the
heating nor the air conditioning is engaged. On a rise in temperature
to the cooling setpoint, the air conditioning comes on, and conversely
on a fall to the heating setpoint, the heat comes on.
So what’s the point? Well, to finally explain the title of this short
story, setpoints such as these are often “seasonal”. In the summer, a
cooling setpoint of 72 degrees may be suitable, however in the winter,
a heating setpoint of 70 may be considered “too low”. So you go to the
thermostat and kick the overall setpoints up two degrees. The moral of
the story is, your thermostat may need to be adjusted on a seasonal
basis, in order to satisfy your personal preference.
The Truth Behind Economizers
One of the most clever features of a typical, standard rooftop unit,
and perhaps also one of the most misunderstood, is the economizer
section. The economizer section of a rooftop unit, or for any air
handler for that matter, is designed to utilize outside air as a source
of “free cooling” if outside air conditions permit. This is done by
modulating the outside and return air dampers to bring in the proper
amount of cool, dry outside air. The colder (and less humid) it is
outside, the more of an opportunity there is to economize.
[an error occurred while processing this directive]
The decision on whether to economize or not is based on the “condition”
of the outside air. If it’s 80 degrees outside, there’s no opportunity
for economizer operation. Humidity is another factor to consider in
making the decision to economize. If it’s cool yet humid outside, we
don’t want to use the outside air for free cooling, if at the same time
we’d be contributing to an indoor humidity problem. On the other hand,
if it’s warm and dry outside, the use of outside air may be at least
partially beneficial to the cooling needs of the space served. An
enthalpy controller is utilized to determine the value of the outside
air, in terms of its cooling ability.
Once the decision is made to economize, and a call for cooling has been
requested by the space thermostat, then economizer operation is
implemented. It is to be noted that the rooftop unit’s refrigeration
cycle, i.e., DX cooling, will not necessarily be entirely disabled, for
there are instances where the outside air, although beneficial to the
cooling process, may not be sufficient to completely satisfy the
cooling needs of the space. In other words, these two processes
(economizer operation and DX cooling) are not mutually exclusive.
Sometimes those new to the concept tend to mistakenly interpret it that
way. The fact is, economizer and DX may both be implemented at the same
time, if that’s what’s called for to satisfy setpoint. For example, if
the outside air is 60 degrees and dry, the enthalpy controller may
permit the use of the economizer, and the 60-degree air definitely
helps the cause. However 60 degrees into the space may not be adequate
to satisfy the thermostat, and so the stat calls for more, and what do
you get? Yep, DX cooling to the rescue!
Tip of the Month: Challenge yourself to find your comfort range. Find
your optimal temperature, then tweak it down, one degree at a time,
until you find yourself shivering off the chill. Then tweak it upward,
again one degree at a time, until you start to sweat. You may be
surprised, either by how wide it is, or more likely, by how narrow!
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The Automator] [About] [Subscribe ] [Contact Us]