March 2014
Column
AutomatedBuildings.com

BTL Mark: Resolve interoperability issues & increase buyer confidence
BACnet Testing Laboratories

(Click Message to Learn More)


Controls Optimization

– No Longer Optional

Paul Ehrlich, Ira Goldschmidt & Angela Lewis
Building Intelligence Group

As published
Engineered Systems 
March Issue - BAS Column

Articles
Interviews
Releases
New Products
Reviews
ABB
Editorial
Events
Sponsors
Site Search
Newsletters
Secured by Cimetrics
Archives
Past Issues
Home
Editors
eDucation
Control Solutions, Inc
Training
Links
Software
Subscribe
Securing Buildings News

At one time, it might have been acceptable to view controls as a “necessary evil” with little attention given to the details of design including sequences and commissioning.  To deliver high performance buildings today requires systems optimization with special detailed attention to controls design and delivery.  As state energy codes move to the latest versions of ASHRAE 90.1, even conventional new buildings will need to be high performance.  This moves controls design to being a necessity to help meet required performance.

This month we are going to look at some of the key optimization strategies that you should consider for both current and upcoming projects.

General:

There are a few fundamental concepts we always come back to in order to optimize any system.  These include:

  1. Operate to Meet Occupancy:  Systems should provide required comfort and ventilation levels when an area is occupied.  When it isn’t occupied, turn off the lights, stop ventilating, and hold temperatures at a safe, unoccupied level.  This can be extended to include modifying ventilation levels to match occupancy.
  2. Don’t Heat and Cool at the Same Time:  Avoid, or at least minimize the use of reheat and other strategies that heat and cool the same air stream.
  3. Use the Most Efficient Energy Source:  This includes the use of high efficiency equipment such as chillers, boilers and fans as well as the use of economizers for “free cooling” whenever possible. It also extends to the most efficient heat rejection as possible including the use of towers, ground source, and evaporative cooling.
  4. Deliver BTU’s Efficiently:  Only move as much air or water needed to deliver comfort.  For most systems, this means the use of variable flow systems that only move what is required. 

From the above four fundamental strategies, you can then develop a series of optimization strategies.  Note that not all of these strategies apply to every project, and these do not include all of the necessary strategies and sequences required for proper and safe operation.

Air Side:  These are strategies that are applied to airside systems including both applied and unitary air handling equipment and their associated terminal units.

Static Pressure Reset:  The supply fan speed is varied so that it only provides enough air to satisfy the most demanding VAV terminal.  This is achieved by controlling the fan to meet a static pressure setpoint, which is dynamically reset based on the most extreme box position.  This strategy matches both airflow and static pressure to meet the demands of the system.

Supply Air Reset:  Raise the supply air setpoint when the majority of boxes are in their heating mode.  This strategy balances out the need for reheating while still holding down fan energy usage.

Demand Controlled Ventilation:  Adjust the People Outdoor Air Rate (Rp) based on building occupancy. This is generally done with the use of CO2 sensing but other mechanisms for occupant counting can also be used.

Single Zone VAV:  Utilize a VFD on a single zone air handler and modulate the fan speed, along with discharge air temperature, to meet the zones demands.

Occupancy Based Control:  Schedule based on occupancy, down to the zone level.  This can be done by scheduling groups of VAV terminals, or with the use of occupancy sensors.  Look for opportunities to coordinate occupancy to also schedule lighting.

contemporary Economizer Optimization:  Whenever possible, utilize outdoor air for cooling.  Strategies for economizer changeover can provide more hours of economizer operation reducing the load for mechanical cooling.

Central Energy Plant:  The central energy plant may include chillers, boilers, pumps and towers. 

Chiller and Boiler Sequencing:  Select the most efficient machine(s) to meet the plant load.  This requires information about the plant load, machine efficiency and availability. 

Condenser Water Reset:  For water cooled systems, balance energy use between the towers and chillers to minimize overall energy usage by placing as much work as possible onto the cooling towers.

Variable Primary Flow:  Only move as much water as needed to meet the building-cooling load.  The use of variable primary flow is the most efficient option.  Proper control requires control of system static.  Measurement and control of plant flow is also highly recommended.

Following the basics and developing the required optimization sequences are invaluable for high performance building operations.  To make these viable though requires careful design including detailed sequences and points lists.  Finally, controls commissioning to verify proper operations is essential!


About the Authors

Paul and Ira Paul and Ira first worked together on a series of ASHRAE projects including the BACnet committee and Guideline 13 – Specifying DDC Controls. The formation of Building Intelligence Group provided them the ability to work together professionally providing assistance to owners with the planning, design and development of Intelligent Building Systems. Building Intelligence Group provides services for clients worldwide including leading Universities, Corporations, and Developers. More information can be found at www.buildingintelligencegroup.com  We also invite you to contact us directly at Paul@buildingintelligencegroup.com or ira@buildingintelligencegroup.com


footer

Reliable Controls
[Click Banner To Learn More]

[Home Page]  [The Automator]  [About]  [Subscribe ]  [Contact Us]

Events

Want Ads

Our Sponsors

Resources