September 2011
Interview
AutomatedBuildings.com
|
[an error occurred while processing this directive]
(Click
Message to Learn More)
|
EMAIL
INTERVIEW
– Len Damiano and Ken
Sinclair
Len Damiano, Vice President - Marketing &
International Sales, EBTRON
ASHRAE 62.1-2010 and CO2-based DCV
The actual determinant of space ventilation rate
(Vbz in the 62.1 procedure) is population. CO2 control proponents
mostly ignore that fact and prefer to focus your attention on odor and
human bioeffluents.
Sinclair: There appear to be many sensing, application and methodology issues to
overcome. Why do CO2 control supporters believe this method
works?
Damiano:
Allow me to explain and challenge some of the justifications of CO2 lone-input methods.
1. CO2 directly addresses only the “people component”
of 62.1 rate tables and has no direct and no indirect relationship to
the “area component” of the rate tables. The only relationship
that exists is with “rate/person” through the assumptions highlighted
in the Steady-State formula. To make this leap for control
purposes requires the acceptance of large uncertainties in outdoor air
control set point maintenance, together with deliberate over
ventilation (through theoretical calculations or “worst-case”
assumptions) as populations change.
With the addition of the “area” component in 2002, the minimum
ventilation requirement varies nonlinearly with changes in population
and is unique to the size and type of occupancy of the space
involved. Providing “less than that required” by the Ventilation
Rate Procedure is almost a certainty under some operating
conditions. This forces the use of a “worst-case” assumption or a
nonlinear algorithm using multiple set points, a different one for
every space monitored then individually written into custom controller
software.
Consideration must also be made for ventilation in excess of that
required for the population, to compensate for all sources of potential
measurement error (indoor sensor, fixed outdoor CO2 concentrations, and
occupant activity level), in an attempt to prevent the intake rate from
falling below the prescribed minimums stated in the Standard.
Thereafter, intake rate performance will still be limited to the
cumulative measurement and hardware errors of the CO2 sensors, together
with the uncertainty related to how they may be applied (sampling
error, etc.). There is no requirement in the Standard limiting
excessive ventilation, so efficiency is not addressed..
2. The actual determinant of space ventilation rate
(Vbz in the 62.1 procedure) is population. CO2 control proponents
mostly ignore that fact and prefer to focus your attention on odor and
human bioeffluents. However, CO2 can be used to estimate space
population in steady-state or transient conditions provided that
dynamic outdoor air intake rates and zone supply rates are also known
(Mumma 2005, et.al.). Population determination with CO2 should
not be excluded due to the lack of steady-state conditions, but rather
due to the lack of input on the additional variables needed to address
all of the relationships required in the Steady-state relationship –
namely outdoor air intake rates and/or supply air rates – depending on
the method selected and the type of system involved.
Multi-zone control with ventilation reset for a variable population is
possible, but not without precise airflow inputs. There are at
least three potential methods (EBTRON 2004). All of these
multiple input control methods carry the uncertainties associated with
CO2 concentration measurement, but modeling has shown them to be far
superior in ventilation control performance than CO2 inputs alone.
However imprecise, there are applications where CO2 is the best choice
to indicate changes in population. Control acceptability with CO2
inputs and code compliance to “not less than” a fixed value, are
totally different animals. They cannot be equated easily.
3. The cost for CO2 sensors, wiring, installation and
control software should exceed the cost of simpler and more reliable
alternatives (time schedules, binary occupancy sensors, existing
counting systems, etc.). CO2–based DCV will increase the
engineer’s risk and extend his liability if the system does not operate
as reliably or efficiently as expected.
4. Most central to the problem is the conclusion that
controlling bioeffluents is a valid objective of the Standard (62.1)
and that it may be equated to controlling intake rates for dilution
ventilation. Yes, the original chamber studies in the 1930’s did
focus on odor control, but only to establish a range of levels required
to dilute it. By extension, those rates were assumed to also
dilute other indoor contaminants. Without some direct measure we
can never be sure that the calculated design rate will be sufficient
during operation for compliance with rate-based standards and
codes. A lack of odor does not satisfy the Ventilation Rate
Procedure in ASHRAE 62.1-2010, and the measurement of CO2 alone does
not satisfy the IAQ Procedure. The objective of the standard has
always been “to specify minimum ventilation rates” as stated in its
published Purpose since 1989 and never to limit indoor bioeffluents,
(although the basis for the rates was influenced by the relationship
between odors and bioeffluents, odors and ventilation
rates/person).
[an error occurred while processing this directive]
If we did want to relate odors to ventilation rates, then using indoor
carbon dioxide concentration measurement does not appear to be the way
to do it. The conclusions of the original researchers in 1936
speak directly to the use of CO2, relating to the adequacy of
ventilation for odor control:
“Among the more significant conclusions arrived at by these researchers were the following:
1. Outdoor air requirements can be determined by gauging the odor produced.
9. Carbon dioxide concentration is an unreliable
index of adequate ventilation because its concentration is not
proportional to the odor intensity produced. “
C.P. Yaglou, E.c. Riley and D.I. Coggins, 1936, Ventilation Requirements, ASH&VE Transactions, Vol. 42, p.133, 1936.
5. Another problem is that the minimum, worst-case,
flow rate is allowed to be determined with a one-time manual
measurement and a predetermined fixed position on a 2-position or
modulating damper. Neither of the measurement variables in this
method of rate determination are sufficiently repeatable to ensure
compliance and efficiency due to damper/actuator hysteresis and
actuator resolution limitations.
These conclusions were demonstrated in full-scale testing with
high-quality aluminum airfoil dampers that a 30 – 50% change in flow
rate was possible based solely on system linkage hysteresis and later
verified in full-scale system testing with full instrumentation (EBTRON
1999, 2008). The results apply to both CV and VAV systems that
use this intake control philosophy. It is still somehow allowed
by codes and standards for constant volume systems, dramatizing the
ineffectiveness of the CV exceptions to intake reset and controls.
The effect of fixed intake damper control, comparing conditions at
start up to operation, was modeled and published in an ASHRAE Journal
article almost 22 years ago (Solberg, AJ, Jan 1990). The industry
eventually accepted the vulnerability of flow rates to fixed intake
damper use on VAV systems with addendum “u” of ASHRAE Standard 62-2001,
Section 5.3 Ventilation System Controls, in Jan. 2002:
“The system shall be designed to maintain minimum outdoor airflow as
required by Section 6 under any load condition. Note: VAV systems with
fixed outdoor air damper positions must comply with this requirement at
minimum supply airflow.
A recently ANSI-approved addendum (‘62.1-s’ in 2011) makes the point on
fixed damper control even stronger by being placed directly in the body
of the standard. The addendum requires modulating dampers or a
modulating injection fan in VAV systems. By its absence as a
means of compliance, it strongly discourages fixed position dampers in
all but the most conservative worst-case design assumptions needed to
satisfy 5.3.1. This change will be published in the 2012
Supplement to the Standard.
Finally, Demand Controlled Ventilation is NOT synonymous with the use
of CO2 for intake reset control. CO2 is merely one of several
possible inputs or methods that can be used to indicate a change in
population. The latest version of 62.1 includes a new section
(§6.2.7) on Dynamic Reset which includes Demand Controlled
Ventilation. It defines DCV as follows: “any means by which
the breathing zone outdoor air flow (Vbz) can be varied to the occupied
space or spaces based on the changing number of occupants and/or
ventilation requirements of the occupied zone.” Please refer to
section 6.2.7 in the standard for additional details.
The indirect control of intake rates, regardless of the proxy used, are
loaded with compounding uncertainties that regulate the controlled
variable – OA intake rates. The indirect agent, in this case CO2
and the bioeffluents it represents, should never be confused with the
approved purpose of the standard and the primary variable – ventilation
rates. Neither should the convenience of a control method be
tolerated if it also brings excessive uncertainties which can
circumvent the intent of the Standard and energy inefficiencies during
operation that are sure to follow.
DCV is required for high density spaces and can help to satisfy both
Standard 90.1 and CA Title 24 energy codes, but in very specific
situations. There is currently no supporting data to allow
its use as the sole input to control ventilation in a multi-zone
building. CO2 usage does not relieve the engineer from the
responsibility of finding ways to satisfy both energy and IAQ
objectives, simultaneously.
Only with inappropriately applied assumptions (or the use of creative
justifications), can one conclude that CO2-based DCV can be used to
satisfy the intent of Standards 62.1, 90.1, 189.1 or CA Title 24
without grossly over ventilating the occupied space.
Sinclair: Where can we find a complete copy of the white paper?
Damiano: A 20-page paper on ASHRAE Standard 62.1-2010 may be found and
downloaded at
http://ebtron.com/Web_Pdfs/SPSync/Vertical%20Marketing/White%20Papers/ASHRAE_62.1_1_Analysis.pdf
footer
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The
Automator] [About] [Subscribe
] [Contact
Us]