ATLANTA – Public comment is being sought on the proposed allowance of
an additional default value to the ventilation rate procedure in
ASHRAE’s indoor air quality standard.
ANSI/ASHRAE Standard 62.1-2010, Ventilation for Acceptable Indoor Air
Quality, sets minimum ventilation rates and other requirements for
commercial and institutional buildings. The ventilation rate
procedure provides a prescriptive method for determining minimum
ventilation requirements. It accounts for pollutant sources from both
the building and its occupants, and allows the designer to account for
the efficiency of different ventilation systems when delivering outdoor
air to the breathing zone.
Some users of Standard 62.1 believe that the ventilation rate procedure
is “too complicated,” according to Standard 62.1 chair Roger Hedrick.
“While the 62.1 committee disagrees with this in most cases – the
basics of the VRP are quite straightforward – the committee agrees that
application of the multiple-zone recirculating system equations
described in Section 6.2.5 and Appendix A can be complex.”
Proposed addendum f, open for public review until Oct. 16, provides an additional default value for Vpz.
"Difficulty determining an appropriate value for Vpz seems to be a
frequent issue with users of the multiple space equations,” he said.
“The committee decided that supplying a default value would simplify
application. However, the default value is necessarily
conservative. In a large number of applications, determining the
'lowest zone primary airflow value expected at the design condition
analyzed' will result in a value for Vpz that is higher than the
default, resulting in a reduced outdoor air intake
requirement."
[an error occurred while processing this directive]Addendum f is open for public review until Oct. 16, 2011, along with
proposed addendum h. Also, proposed addendum g to the standard is open
for public review until Oct. 31, 2011. For more information, visit
www.ashrae.org/publicreviews. The other addenda open for public review
are:
• Addendum h (until Oct. 16). Table 6.1 in the
standard includes ventilation rates for “Sports arena (play area)” and
“Gym, stadium (play area).” Both space types have ventilation
rates based on floor area only, with a per person rate of zero.
Users of the standard have expressed interest in applying demand
controlled ventilation to these space types, which is effectively
prohibited by the lack of a per person component to the ventilation
rate. This proposed addendum replaces both of these space types
with “Gym, Sports Arena (play area),” with Rp = 20 cfm/person and Ra =
0.06 cfm/ft². In most cases, the overall ventilation rate for
these spaces is expected to decrease, possibly significantly, according
to Hedrick.
One concern about allowing CO2-based demand controlled ventilation in
these spaces is that the volume per person in these spaces is typically
large, which means that CO2 concentration changes will have longer than
usual lag times behind occupancy changes, he noted.
• Addendum g (open until Oct. 31). Currently
users are directed that for space types that are not listed in Table
6-1 they should select the space type from the table that is most
similar to the space being designed. However, some space types
are actually ventilated using the exhaust ventilation requirements of
Section 6.5 and Table 6-4. This proposed addendum adds language
directing the user to select the space type that is most similar to the
space in question from either Table 6-1 or 6-4, and to design the
ventilation for the space according to the Section 6.2 or 6.5, as
appropriate
ASHRAE, founded in 1894, is an international organization of some
50,000 persons. ASHRAE fulfills its mission of advancing heating,
ventilating, air conditioning and refrigerating to serve humanity and
promote a sustainable world through research, standards writing,
publishing and continuing education. For more informationn about ASHRAE visit http://www.ashrae.org.