January 2011 |
[an error occurred while processing this directive] |
Systems & Sequences
Waterside systems Part 2 of 2 |
Steven R. Calabrese |
With the holidays approaching, as everyone else I find myself pressed
for time as I write this column. As promised last month, I present part
two in a two-part series on systems and sequences…maybe part two being
a little bit shorter than part one. ( Part 1 of 2 ) But that’s the price I pay for
waiting till the last minute to get my shopping done!
Articles |
Interviews |
Releases |
New Products |
Reviews |
[an error occurred while processing this directive] |
Editorial |
Events |
Sponsors |
Site Search |
Newsletters |
[an error occurred while processing this directive] |
Archives |
Past Issues |
Home |
Editors |
eDucation |
[an error occurred while processing this directive] |
Training |
Links |
Software |
Subscribe |
[an error occurred while processing this directive] |
So in part one, I covered airside systems, which included packaged
rooftop units, fan coil units, VAV air handling units, and terminal
units (VAV & fan-powered boxes). For each topic, I described the
system in terms of sequence of operation and specification
requirements, followed by a listing of do’s and don’ts regarding
control system design and operation. In this part of the series, I
follow the same format, and discuss waterside systems (pumps, boilers,
and chillers).
Pumping Systems
Sequence Items
There are multitudes of various pumping systems to consider, so we’ll
just consider the popular two-pump system, with each pump sized at full
capacity, meaning that either pump can handle the full GPM requirements
of the system that its serving, with the other pump standing by in the
event of failure of the primary operating pump. I case you missed it,
this is referred to as “primary/standby”, or “primary/backup”
operation. The pumping system can be constant or variable volume, where
in the case of variable volume, the pumps would be equipped with
variable frequency drives (VFDs), and the drives would be controlled to
vary the motor speed, and hence the GPM rate, of the pumping system.
This is typically done by monitoring the differential pressure in the
supply and return mains, establishing a suitable pressure setpoint, and
ramping the VFD up and down as required to maintain setpoint. For
either type system (constant or variable volume), there is typically a
“seasonal” changeover function, meaning that, at some point in the
calendar year, or perhaps based upon the outside air temperature, the
pumping system is disabled. For hot water pumping systems, this would
happen in the springtime, and for chilled water pumping systems, it
would happen in the fall.
Do’s & Don’ts
For this type of pumping system, do specify automatic alternation,
meaning that the pumps alternate from primary to backup (and vice
versa) based on a schedule or based on run-time hours. This gives each
pump equal service, and helps to ensure even wear on the pumps. Don’t
specify a single, common flow switch or differential pressure switch to
indicate flow status. These days it’s more common anyway to fit each
pump motor with a current sensing switch. No, you’re not directly
monitoring the presence or absence of flow, but it’s still a pretty
reliable indicator of such, and has become the industry standard for
monitoring pump operation.
Boiler Systems
Sequence Items
Boiler systems function to maintain hot water temperature setpoint
(whatever that may be). For systems with multiple boilers, the boilers
are sequenced to meet demand, meaning that if one boiler can’t maintain
system setpoint, the next boiler is pressed into operation. The boilers
themselves either operate from their own controls, or are
staged/modulated via external control, by either a manufactured boiler
sequencer panel, or by Direct Digital Control (DDC).
Do’s & Don’ts
For energy conservation and control optimization purposes, do specify
outdoor air reset control. This dictates that as the outside air
temperature increases, the hot water temperature setpoint is decreased,
or “reset” downward. And for boilers that are not direct vented, do
prove combustion air before allowing boiler operation. This typically
entails commanding open a motorized combustion air damper, and
monitoring the end switch on the motor to verify that the motor has
indeed stroked fully. Don’t specify unoccupied mode shutdown for hot
water boilers. And don’t turn off the pumps until the boilers are
allowed to cool down. In other words, incorporate a delay whereupon
shutdown of the boiler system would allow the pumps to continue to run
for a short period of time, to dissipate the residual heat within the
boiler plant.
[an error occurred while processing this directive]Chiller Systems
Sequence Items
Chiller systems function to maintain chilled water temperature
setpoint. As with boiler systems, if there are multiple machines, then
the chillers are sequenced to meet chilled water demand. Chillers
operate from their own controls; chiller manufacturers equip their
chillers with specialized control systems that meet the requirements of
the mechanical equipment being controlled. In this sense, chillers are
packaged equipment, saying that all required controls components, with
the exception of a few “loose controls” that have to be
field-installed, come standard as “part of the package”.
Do’s & Don’ts
As discussed above, chillers are basically packaged equipment, however
there is one feature that chiller manufacturers have built in to their
control systems, and that is the ability to accept an external setpoint
signal. So do specify a setpoint signal from the Building Automation
System (BAS), such that the BAS can determine and set the proper
chilled water temperature setpoint at any given time under any given
load or operating condition. Don’t vary the chilled (or condenser)
water flow through the chiller, below the manufacturer’s recommended
minimum. These days there is a push to equip all motors with VFDs, and
that’s fine, however certain applications merit special attention, and
chilled water pumping is one of them. Again, identify the
manufacturer’s requirement for the minimum allowable GPM rate, and
adhere to that requirement.
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The Automator] [About] [Subscribe ] [Contact Us]