July 2009 |
[an error occurred while processing this directive] |
Advanced Controls Optimization for High Performance Buildings Strategies that should be considered to optimize the operations of these systems using the control system to dramatically reduce energy usage. |
Paul Ehrlich & Ira Goldschmidt |
As a regular reader of Engineered Systems you likely have a pretty good understanding of temperature controls and building automation (BAS). This includes the design and operation of VAV air handling systems as well as chiller plants and rooftops. Over the next two columns we are going to look at strategies that should be considered to optimize the operations of these systems using the control system to dramatically reduce energy usage.
[an error occurred while processing this directive] |
[an error occurred while processing this directive] |
Part I: Air Side Controls
We can characterize the traditional control of VAV systems as using closed loop control for delivery of a constant pressure, and temperature of air, with a consistent percentage of ventilation and a variable flow based on VAV terminal demand. It is possible, however, with the use of advanced control algorithms to significantly improve the efficiency of these systems resulting in many dramatic reductions in energy usage, and improved comfort. How is this possible? The answer is systems optimization. Let’s look at some examples of common strategies:
Static Pressure Reset:
Using a static pressure sensor and a variable frequency drive on a VAV air
handler provides for significant energy savings compared to constant volume
operation. However controlling to a fixed duct static pressure set-point is
problematic. Challenges include both properly locating the sensor as well as
determining the correct set-point. On many project sites VAV systems provide
more static pressure then is needed, resulting in both higher energy use and
problems with box control and fan noise. So what is the correct static pressure
set-point? The answer is that it doesn’t matter – the fan needs to produce only
enough pressure to serve the most extreme box but not too much pressure as to
possibly damage the ductwork. The static pressure reset algorithm looks at VAV
box valve position to determine the optimal static set-point for proper system
operation. Allowances are typically made for disregarding “extreme zones” that
may have undersized boxes. Using this strategy allows for greater flexibility in
static sensor placement, can help reduce fan noise and is estimated to reduce
total HVAC energy usage by 2% to 4%.
[an error occurred while processing this directive]
Supply Air Temperature Reset:
In addition to resetting the duct static pressure, strategies can
also be utilized to reset the discharge temperature set-point of the air handler
based on the temperature of the individual zones. Increasing the discharge
temperature does reduce the amount of energy used by the chiller plant; however
it will typically result in an increase in fan energy. Caution needs to be used
to both balance the energy savings (through the use of energy modeling) and also
to be sure that adequate de-humidification is being achieved.
Demand Controlled Ventilation
In order to maintain a healthy ventilation level, ASHRAE Standard 62
specifies a fixed ventilation level for removal of contaminants and an
additional amount of ventilation to disperse the CO2 impact of the occupants.
During normal operation the building is kept ventilated based on the anticipated
design occupancy. The standard does, however, allow for an alternate control
strategy which measures the actual occupancy (typically through the use of CO2
sensors) and measures and adjusts ventilation to reflect actual occupancy. This
strategy most importantly results in a healthy indoor environment and also can
provide significant energy savings. Energy savings will vary depending on the
building location and occupancy and can be calculated using broadly available
tools. HVAC energy savings for office buildings are in the range from a low of
3% to 20% or higher.
Next Month: Water Side Control Optimization
About the Authors
Paul
and Ira first worked together on a series of ASHRAE projects including the
BACnet committee and Guideline 13 – Specifying DDC Controls. The formation of
Building Intelligence Group provided them the ability to work together
professionally providing assistance to owners with the planning, design and
development of Intelligent Building Systems. Building Intelligence Group
provides services for clients worldwide including leading Universities,
Corporations, and Developers. More information can be found at
www.buildingintelligencegroup.com We also invite you to contact us
directly at
Paul@buildingintelligencegroup.com or
ira@buildingintelligencegroup.com
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The Automator] [About] [Subscribe ] [Contact Us]
[an error occurred while processing this directive]
[Click Banner To Learn More]
[Home Page] [The Automator] [About] [Subscribe ] [Contact Us]